rac on - rac on
Typology: Exercises
1 / 20
This page cannot be seen from the preview
Don't miss anything!
At the end of the lecture, the student should be able to:
Vapour Absorption Refrigeration Systems (VARS) belong to the class of vapour cycles similar to vapour compression refrigeration systems. However, unlike vapour compression refrigeration systems, the required input to absorption systems is in the form of heat. Hence these systems are also called as heat operated or thermal energy driven systems. Since conventional absorption systems use liquids for absorption of refrigerant, these are also sometimes called as wet absorption systems. Similar to vapour compression refrigeration systems, vapour absorption refrigeration systems have also been commercialized and are widely used in various refrigeration and air conditioning applications. Since these systems run on low-grade thermal energy, they are preferred when low-grade energy such as waste heat or solar energy is available. Since conventional absorption systems use natural refrigerants such as water or ammonia they are environment friendly.
Water at 30 oC 50% LiBr soln. at 30oC
4.24 kPa 1.22 kPa
Valve closed
1.22 kPa 1.22 kPa
Water at 10 oC 50% LiBr soln. at 30oC
Valve open
Water vapour
Q (^) e Q (^) c
30 o^ C
30 o^ C
U a) Initial condition
A
A B
b) Refrigeration
Thus at initial equilibrium condition, the pressure in vessel A is 4.24 kPa, while it is 1.22 kPa in vessel B. Now the valve between vessels A and B is opened. Initially due to pressure difference water vapour will flow from vessel A to vessel B, and this vapour will be absorbed by the solution in vessel B. Since absorption in this case is exothermic, heat will be released in vessel B. Now suppose by some means the concentration and temperature of vessel B are maintained constant at 50 % and 30oC, respectively. Then at equilibrium, the pressure in the entire system (vessels A and B) will be 1.22 kPa (equilibrium pressure of 50 % LiBr solution at 30 oC). The
Weak LiBr soln. at Tg
Q (^) c Q (^) g
Water at 30 oC
Water vapour
c) Regeneration
Valve open
4.24 kPa 4.24 kPa
30 o^ C
Fig.14.1 : Basic principle of vapour absorption systems
temperature of water in vessel A will be the saturation temperature corresponding to 1.22 kPa, which is equal to about 10oC, as shown in the figure. Since the water temperature in A is lower than the surroundings, a refrigeration effect (Qe) can produced by transferring heat from the surroundings to water at 10oC. Due to this heat transfer, water vaporizes in A, flows to B and is absorbed by the solution in B. The exothermic heat of absorption (Qa) is rejected to the surroundings.
Now for the above process to continue, there should always be pure water in vessel A, and vessel B must be maintained always at 50 percent concentration and 30 oC. This is not possible in a closed system such as the one shown in Fig.14.1. In a closed system with finite sized reservoirs, gradually the amount of water in A decreases and the solution in B becomes diluted with water. As a result, the system pressure and temperature of water in A increase with time. Hence the refrigeration effect at A reduces gradually due to the reduced temperature difference between the surroundings and water. Thus refrigeration produced by systems using only two vessels is intermittent in nature. In these systems, after a period, the refrigeration process has to be stopped and both the vessels A and B have to be brought back to their original condition. This requires removal of water absorbed in B and adding it back to vessel A in liquid form, i.e., a process of regeneration as shown in Fig.14.1(c).
Assume that before regeneration is carried out, the valve between A and B is closed and both A and B are brought in thermal equilibrium with the surroundings (30oC), then during the regeneration process, heat at high temperature Tg is supplied to the dilute LiBr solution in B, as a result water vapour is generated in B. The vapour generated in B is condensed into pure water in A by rejecting heat of condensation to the surroundings. This process has to be continued till all the water absorbed during the refrigeration process (14.1(b)) is transferred back to A. Then to bring the system back to its original condition, the valve has to be closed and solution in vessel B has to be cooled to 30oC. If we assume a steady-flow process of regeneration and neglect temperature difference for heat transfer, then the temperature of water in A will be 30 oC and pressure inside the system will be 4.24 kPa. Then the temperature in vessel B, Tg depends on the concentration of solution in B. The amount of heat transferred during refrigeration and regeneration depends on the properties of solution and the operating conditions. It can be seen that the output from this system is the refrigeration obtained Qe and the input is heat supplied to vessel B during vapour regeneration process, Q (^) g.
The system described may be called as an Intermittent Absorption Refrigeration System. The solvent is the refrigerant and the solute is called as absorbent. These simple systems can be used to provide refrigeration using renewable energy such as solar energy in remote and rural areas. As already explained, these systems provided refrigeration intermittently, if solar energy is used for regenerating the refrigerant, then regeneration process can be carried out during the day and refrigeration can be produced during the night.
Though the intermittent absorption refrigeration systems discussed above are simple in design and inexpensive, they are not useful in applications that require continuous refrigeration. Continuous refrigeration can be obtained by having a modified system with two pairs of vessels A and B and additional expansion valves and a solution pump.
converted into a liquid and then the liquid is pumped to condenser pressure using the solution pump. Since for the same pressure difference, work input required to pump a liquid (solution) is much less than the work required for compressing a vapour due to
very small specific volume of liquid ( ), the mechanical energy required to
operate vapour absorption refrigeration system is much less than that required to operate a compression system. However, the absorption system requires a relatively large amount of low-grade thermal energy at generator temperature to generate refrigerant vapour from the solution in generator. Thus while the energy input is in the form of mechanical energy in vapour compression refrigeration systems, it is mainly in the form of thermal energy in case of absorption systems. The solution pump work is often negligible compared to the generator heat input. Thus the COPs for compression and absorption systems are given by:
Pc
Pe
w v.dP
c
e VCRS W
g
e g p
e VARS Q
Thus absorption systems are advantageous where a large quantity of low-grade thermal energy is available freely at required temperature. However, it will be seen that for the refrigeration and heat rejection temperatures, the COP of vapour compression refrigeration system will be much higher than the COP of an absorption system as a high grade mechanical energy is used in the former, while a low-grade thermal energy is used in the latter. However, comparing these systems based on COPs is not fully justified, as mechanical energy is more expensive than thermal energy. Hence, sometimes the second law (or exergetic) efficiency is used to compare different refrigeration systems. It is seen that the second law (or exergetic) efficiency of absorption system is of the same order as that of a compression system.
In case of a single stage compression refrigeration system operating between constant evaporator and condenser temperatures, the maximum possible COP is given by Carnot COP:
c e
e Carnot T T
If we assume that heat rejection at the absorber and condenser takes place at same external heat sink temperature To, then a vapour absorption refrigeration system operates between three temperature levels, Tg, T (^) o and Te. The maximum possible COP of a refrigeration system operating between three temperature levels can be obtained by applying first and second laws of thermodynamics to the system. Figure 14. shows the various energy transfers and the corresponding temperatures in an absorption refrigeration system.
Tg
Te
From first law of thermodynamics,
Q (^) e + Qg−Qc+ a+Wp= 0 (14.4)
where Qe is the heat transferred to the absorption system at evaporator temperature Te, Qg is the heat transferred to the generator of the absorption system at temperature Tg, Qa+c is the heat transferred from the absorber and condenser of the absorption system at temperature To and Wp is the work input to the solution pump.
From second law of thermodynamics, ΔS (^) total =ΔSsys+ΔSsurr≥ 0 (14.5)
where ΔStotal is the total entropy change which is equal to the sum of entropy change of the system ΔSsys and entropy change of the surroundings ΔSsurr. Since the refrigeration system operates in a closed cycle, the entropy change of the working fluid of the system undergoing the cycle is zero, i.e., ΔS (^) sys = 0. The entropy change
of the surroundings is given by:
o
ac g
g e
e Δ (^) surr =− − + ≥
Substituting the expression for first law of thermodynamics in the above equation
p e
o e e g
g o g W T
Neglecting solution pump work, Wp; the COP of VARS is given by:
g
g o o e
e g
e VARS (^) T
Pump
Cycle
Qg
Qe
Qa Qc
W p
System
To
Fig.14.3 : Various energy transfers in a vapour absorption refrigeration system
The solution used in absorption refrigeration systems may be considered as a homogeneous binary mixture of refrigerant and absorbent. Depending upon the boiling point difference between refrigerant and absorbent and the operating temperatures, one may encounter a pure refrigerant vapour or a mixture of refrigerant and absorbent vapour in generator of the absorption system. Unlike pure substances, the thermodynamic state of a binary mixture (in liquid or vapour phase) cannot be fixed by pressure and temperature alone. According to Gibbs’ phase rule, one more parameter in addition to temperature and pressure is required to completely fix the thermodynamic state. Generally, the composition of the mixture is taken as the third independent parameter. The composition of a mixture can be expressed either in mass fraction or in mole fraction. The mass fraction of components 1 and 2 in a binary mixture are given by:
1 2
2 2 1 2
1 (^1) m m
m ; m m
m
ξ =
ξ = (14.12)
where m 1 and m 2 are the mass of components 1 and 2, respectively
The mole fraction of components 1 and 2 in a binary mixture are given by:
1 2
2 2 1 2
1 (^1) n n
n ; x n n
n x
where n 1 and n 2 are the number of moles of components 1 and 2, respectively
An important property of a mixture is its miscibility. A mixture is said to be completely miscible if a homogeneous mixture can be formed through any arbitrary range of concentration values. Miscibility of mixtures is influenced by the temperature at which they are mixed. Some mixtures are miscible under certain conditions and immiscible at other conditions. The refrigerant-absorbent mixtures used in absorption refrigeration systems must be completely miscible under all conditions both in liquid and vapour phases.
14.4.1. Ideal, homogeneous binary mixtures
A binary mixture of components 1 and 2 is called as an ideal mixture, when it satisfies the following conditions.
Condition 1: The volume of the mixture is equal to the sum of the volumes of its constituents, i.e., upon mixing there is neither contraction nor expansion. Thus the specific volume of the mixture, v is given by:
v = ξ 1 .v 1 +ξ 2 .v 2 (14.14)
where ξ 1 and ξ 2 are the mass fractions of components 1 and 2. For a binary mixture, ξ 1 and ξ 2 are related by: ξ 1 +ξ 2 = 1 ⇒ξ 2 = 1 −ξ 1 (14.15)
Condition 2: Neither heat is generated nor absorbed upon mixing, i.e., the heat of solution is zero. Then the specific enthalpy of the mixture, h is given by:
h = ξ 1 .h 1 +ξ 2 .h 2 =ξ 1 .h 1 +( 1 −ξ 1 )h 2 (14.16)
Condition 3: The mixture obeys Raoult’s law in liquid phase, i.e., the vapour pressure exerted by components 1 and 2 (Pv,1 and P (^) v,2) at a temperature T are given by:
Pv (^) , 1 =x 1 .P 1 ,sat (14.17) Pv (^) , 2 =x 2 .P 2 ,sat (14.18)
where x 1 and x 2 are the mole fractions of components 1 and 2 in solution, and P1,sat and P2, sat are the saturation pressures of pure components 1 and 2 at temperature T. The mole fractions x 1 and x 2 are related by:
x 1 + x 2 = 1 ⇒x 2 = 1 −x 1 (14.19)
Condition 4: The mixture obeys Dalton’s law in vapour phase; i.e., the vapour pressure exerted by components 1 and 2 (P (^) v,1 and Pv,2) in vapour phase at a temperature T are given by:
Pv (^) , 1 =y 1 .Ptotal (14.20) Pv (^) , 2 =y 2 .Ptotal (14.21)
where y 1 and y 2 are the vapour phase mole fractions of components 1 and 2 and Ptotal is the total pressure exerted at temperature T. The vapour phase mole fractions y 1 and y 2 are related by:
y 1 + y 2 = 1 ⇒y 2 = 1 −y 1 (14.22)
and the total pressure Ptotal is given by:
Ptotal =Pv, 1 +Pv, 2 (14.23)
If one of the components, say component 2 is non-volatile compared to component 1(e.g. component 1 is water and component 2 is lithium bromide salt), then y 1 ≈ 1 and y 2 ≈ 0, Pv,2 ≈ 0, then from Raoult’s and to Dalton’s laws:
Ptotal ≈Pv, 1 =x 1 .P 1 ,sat (14.24)
14.4.2. Real mixtures
Real mixtures deviate from ideal mixtures since:
v ≠ ξ 1 .v 1 +ξ 2 .v 2 (14.25)
Figure 14.7 shows a basic vapour absorption refrigeration system with a solution heat exchanger on a pressure vs temperature diagram. As shown in the figure, low temperature and low pressure refrigerant vapour from evaporator at state 1 enters the absorber and is absorbed by solution weak in refrigerant (state 8). The heat of absorption (Qa) is rejected to an external heat sink at T∞. The solution, rich in refrigerant (state 2) is pumped to the generator pressure (Pg) by the solution pump (state 3). The pressurized solution gets heated up sensibly as it flows through the solution heat exchanger by extracting heat from hot solution coming from generator (state 4). Heat is supplied to this solution from an external heat source in the generator (Qg at Tg), as a result refrigerant vapour is generated (absorbent may also boil to give off vapour in case of ammonia-water systems) at state 5. This high-pressure refrigerant vapour condenses in the condenser by rejecting heat of condensation to the external heat sink (Qc at T∞) and leaves the condenser as a high pressure liquid (state 9). This high pressure refrigerant liquid is throttled in the expansion device to evaporator pressure Pe (state 10) from where it enters the evaporator, extracts heat from low temperature heat source (Qe at Te) and leaves the evaporator as vapour at state 1, completing a cycle. The hot solution that is weak in refrigerant (state 6) leaves the generator at high temperature and is cooled sensibly by rejecting heat to the solution going to the generator in the solution heat exchanger (state 7). Then it is throttled to the evaporator pressure in the throttle valve (state 8), from where it enters the absorber to complete the cycle. It can be seen that though not an essential component, the solution heat exchanger is used in practical systems to improve the COP by reducing the heat input in the generator. A solution heat exchanger as shown in Fig.14.7 is a counterflow heat exchanger in which the hot solution coming from the generator comes in thermal contact with the cold solution going to the generator. As a
ξ 2
h
Δ h (^) mix
h 1
h 2
T = Constant
Ideal solution
Real solution
Fig.14.6 : Enthalpy-concentration behaviour of an ideal mixture and a real mixture with negative deviation from Raoult’s law
result of this heat exchange, less heat input is required in the generator and less heat is rejected in the absorber, thus improving the system performance significantly.
Absorber
Condenser Generator
Evaporator
Basic vapour absorption refrigeration system with solution heat exchanger
Te T∞ (^) Tg
Pe
Pg
Qe
Qa
Qg
Qc
Solution pump
Heat exchanger
Fig.14.7 : Basic vapour absorption refrigeration system with a solution heat exchanger on a pressure vs temperature diagram
The thermodynamic performance of the above system can be evaluated by applying mass and energy balance to each component assuming a steady flow process. In simple theoretical analyses, internal irreversibilities such as pressure drops between the components are generally neglected. To find the performance from the mass and energy balance equations one needs to know inputs such as the type of refrigerant-absorbent mixtures used in the system, operating temperatures, composition of solution at the entry and exit of absorber, effectiveness of solution heat exchanger etc. A simple steady flow analysis of the system will be presented in later sections.
The desirable properties of refrigerant-absorbent mixtures for VARS are:
i. The refrigerant should exhibit high solubility with solution in the absorber. This is to say that it should exhibit negative deviation from Raoult’s law at absorber. ii. There should be large difference in the boiling points of refrigerant and absorbent (greater than 200oC), so that only refrigerant is boiled-off in the generator. This ensures that only pure refrigerant circulates through refrigerant circuit (condenser-expansion valve-evaporator) leading to isothermal heat transfer in evaporator and condenser.
a) Can provide continuous refrigeration b) Provides refrigeration intermittently c) Can work on solar energy alone d) Has no practical application
Ans. b) and c)
a) Requires only thermal energy as input b) Uses a thermal compressor in place of a mechanical compressor c) Does not require a condenser d) Consists of two expansion valves
Ans. b) and d)
a) There is neither expansion nor contraction upon mixing b) The mixing process is exothermic c) The mixing process is endothermic d) Obeys Raoult’s law in liquid phase and Dalton’s law in vapour phase
Ans. a) and d)
a) The mixing process is exothermic b) The mixing process is endothermic c) The actual equilibrium temperature will be less than that predicted by Raoult’s law d) The actual equilibrium temperature will be less more that predicted by Raoult’s law
Ans. a) and d)
a) Exhibit negative deviation from Raoult’s law at absorber b) Exhibit positive deviation from Raoult’s law at absorber c) Have large heat of mixing d) Have large boiling point difference between refrigerant and absorbent
Ans. a) and d)
a) Water-lithium bromide systems are used for refrigeration applications above 0oC only b) Ammonia-water systems can be used for refrigeration applications below 0oC only c) Small ammonia-water systems are used in domestic refrigerators d) Small water-lithium bromide systems are used in room air conditioners
Ans. a) and c)
a) Find the COP of the system and the total heat rejection rate from the system.
b) An inventor claims that by improving the design of all the components of the system he could reduce the heat input to the system to 80 kW while keeping the refrigeration capacity and operating temperatures same as before. Examine the validity of the claim.
Ans.: a) COP = Q (^) e/Qg= 100/160 = 0.625 (Ans.)
Total heat rejection rate = Qa+Qc = Qe+Qg = 100 + 160 = 260 kW (Ans.)
b) According to the inventor’s claim, the COPclaim is given by:
COPclaim = Qe/Qg = 100/80 = 1.
However, for the given temperatures, the maximum possible COP is given by:
g
g o o e
e g max
e ideal VARS T
Substituting the values of operating temperatures, we find that:
g
g o o e
e max ⎟= ⎠
Since COPclaim > COPmax ⇒ Inventor’s claim is FALSE (Ans.)
b) System pressure falls as condensation of water vapour takes place in A. To keep the system pressure constant, vapour has to be generated in B by supplying heat to solution in B. Since the solution in B becomes richer in LiBr (i.e., concentration increases), at the same pressure of 9.0 kPa, the solution temperature in B increases. (Ans.)
c) From the definition of concentration for H 2 O-LiBr solution;
( ) ( ) ( )⎥
L W,i L W, i
W,i W,f L L W,i
L L W,f
L f i M M .M M
x x x
Amount of water transferred from B to A = (MW,i - MW,f)
The factor f is defined as:
W,i W, f
L W,i M M
f
Substituting the above in the expression for Δx and using the definition of concentration, we find that:
f
x x xf xi f (Ans.)
d) Mass of water transferred is 1.0 kg and change in concentration is 0.05. Hence the final concentration is:
xf = x (^) i+ 0.05 = 0.60 + 0.05 = 0.
Substituting this value in the expression for Δx, we find that
x
x f f^ ⎟= ⎠
Hence the initial mass of solution is given by:
( M (^) L + MW,i ) = f.(massof watertransferred) = 13 X 1. 0 = 13 kgs (Ans.)
e) From energy balance of vessel B, the amount of energy transferred to B is given by:
Q (^) B, in = (MB,f.hf − MB,i.hi) + (MW,i − MW,f)h W
Substituting the values of enthalpies and initial and final mass of solution (13 kg and 12 kg, respectively), we find that the heat transferred to B is:
QB,in = 2880 kJ (Ans.) Neglecting the heat transferred during initial sensible cooling of vapour, the total heat transferred at Vessel A is:
QA,out = Amount of water vapour condensed X latent heat of vapourization = 2500 kJ
(Ans.)
The difference in energy transferred at A and B is stored in the form of heat of solution. (Ans.)
f) To reverse the process and arrive at initial condition, the condensed water in vessel A has to be vapourized by supplying heat to vessel A. The vapour generated is absorbed by strong solution in B. Since this is an exothermic process, heat has to be rejected from B. (Ans.)
g) D˘hring plot of forward and reverse processese is shown below:
Forward process
Reverse process